The ZAZM-MI is supplied in a modern enclosure (2 gang box size) with well protected electronic circuit board to minimize any damages during installation. It is supplied with a back box suitable for surface mount indoor installation. Designed and manufactured to meet the requirement of EN54-18 2005 and EN54-17 2005. The ZAZM-MI is a conventional zone that can be used for conventional devices and/or for special detectors that are not available in addressable form such as UV detectors, Aspiration detectors etc. For more details and connection information consult the installation guide.


₵1792.00 

Learn More


FEATURES


  • This is a loop powered device, however loop load calculation must be performed to determine the permissable quantity of ZAZM-MI per loop. 
  • Hand addressed using the 8 way dip switch OR 
  • Softly addressed using our handheld MKII Programmer (part no. 48-004) 
  • Equipped with short circuit line isolator Extensive front unit indications


TECHNICAL SPECIFICATIONS


  • Model ZAZM-MI 
  • Part Number 48-117 
  • Operating Voltage 17 – 28V DC 
  • Quiescent Current 3.5mA 
  • Alarm Current (LED OFF) 12.6 mA 
  • Alarm Current (LED ON) 13.2 mA 
  • Isolating Current 7.3mA 
  • End of Line Resistor 6.2k 
  • Nominal Alarm Triggering Resistor 1k 
  • Operating Temperature "-10C to 55C" 
  • Max Humidity 95% RH Non Condensing 
  • IP Rating IP21C 
  • Size 150 x 90 x 45 mm 
  • Weight 220g